Pressure Regulating Landing Valve

Description
Pressure reducing oblique landing valves are suitable for installation on wet risers in buildings for fire fighting purposes, permanently charged with water from a pressurized supply.These landing valves are pressure reducing type designed to provide a range of outlet pressure (5 bar - 8 bar).The landing valves are classified under high pressure and are suitable for use at nominal inlet pressure upto 20 bar and for working temperature range from 0 °C to 38 °C.

Specification
Standard:Certificate to BS 5041-1 Approve by BSI and LPCB
Body:Copper alloy, Thickness ≥3mm                                                
Hand wheel:Grey cast iron or Aluminum alloy
Black cap:Copper alloy / Plastic                                                          
Inlet:Flanged inlet or BSP Screwed
Outlet:Female instantaneous to BS336      
Size:DN50(2") , DN65(2.5")                                            
Surface:Red or yellow painting
Test pressure:22.5 bar                                                      
Flow rates:More than 8.5L/S
Fully open:4.5 turns
Inlet pressure 20bar,regulating outlet static pressure 5 – 8 bar                                           
Inlet pressure 30bar,regulating outlet static pressure > 20 bar